Professional Industrial Sensor Manufacturer
XSZ Sensor

Sensor Terminology

Sinking Input

Meaning, Working Principle and Wiring Examples

A sinking input is a DC controller input that provides a current path toward the supply return. When a compatible PNP sensor sources current into it, the input circuit can detect an ON signal. The key is to identify the PLC input separately from the sensor output.

Understand the Input →
Illustrative PLC digital input modules with sensor wiring in an industrial control cabinet.
Pairs with PNP
sourcing outputs
Returns current
toward 0 V
Input terminal receives
a positive signal
Used in compatible
DC control modules

What Is a Sinking Input?

A sinking PLC input accepts current from a field device and provides a return path to the DC supply common (0 V). In a typical three-wire arrangement, a PNP sensor sources current from the positive supply into the input when its output is ON. This is a description of current flow through the input circuit, not a claim that every PLC uses the same terminal names or voltage thresholds.

How Does a Sinking Input Work?

In the illustrated DC case, the PLC input circuit sits between the input terminal and a common terminal connected to 0 V. With the PNP output OFF, the sensor does not provide an ON-state current path to that input. When the sensor output turns ON, current flows from +V through the sensor output, into the PLC input circuit and back to 0 V. The module then recognizes the input if its specified ON threshold is met.

Input State — Sensor Output OFF
Simplified circuit: a powered PNP sensor has its output open, so no ON-state current reaches the sinking PLC input; the PLC input common is connected to 0 V.Open full-size diagram ↗

Conceptual state only; check OFF-state leakage and the module's OFF threshold.

Input State — Sensor Output ON
Simplified circuit: current flows from positive DC through the ON PNP output into the sinking PLC input circuit and returns through its common to 0 V.Open full-size diagram ↗

The actual ON voltage and current depend on the specified sensor and input module.

Sinking vs Sourcing Input

The names describe what the input module provides in the field circuit. A sinking input offers a return path to 0 V and is paired with a sourcing (PNP) output. A sourcing input provides a path from +V and is paired with a sinking (NPN) output. Some modules support either configuration when their common is wired appropriately; do not infer that from the word “DC” alone.

ItemSinking PLC InputSourcing PLC Input
Complementary sensor outputPNP, sourcingNPN, sinking
Input current pathFrom field output through input to 0 V commonFrom +V common through input to field output and 0 V
Typical input commonConnected to supply return (0 V)Connected to positive supply (+V)
ON-state field signalPNP output supplies positive voltage/current to inputNPN output pulls input toward 0 V
What to Check
  • Read the input module's exact sink/source wiring diagram.
  • Confirm the common-terminal connection for the input group.
  • Match the sensor output type and the module's DC voltage/current thresholds.
  • Check whether the output function is NO or NC separately.

How Do You Wire a Sensor to a Sinking Input?

The example below uses a three-wire PNP sensor and a DC PLC input specified to accept a sourcing field signal. The sensor positive supply connects to +V; its 0 V lead and the PLC input common return to the same 0 V reference; the PNP output goes to the selected PLC input terminal. Use the actual pinout and input-group manual before installation.

PNP Sensor → Sinking PLC Input
For Contrast: NPN Sensor → Sourcing PLC Input
A common three-wire convention is brown = +V, blue = 0 V and black = switching output, but colors and terminal assignments are model-dependent. Isolate equipment before changing wiring, and follow both manufacturers' instructions.

Where Are Sinking Inputs Used?

Sinking DC inputs can accept signals from compatible PNP sensors in many control tasks. The application determines the sensor technology; the input type only determines part of the electrical interface.

Illustrative optical sensor beside packages on a conveyor for presence or position detection.
Position Detection

A compatible sensor reports the presence or position of a target to the controller.

Illustrative photoelectric sensor beside evenly spaced metal parts on a conveyor for counting events.
Part Counting

A sensor output provides a discrete event for counting parts on a line.

Illustrative industrial instrument mounted on a process vessel for level-indication applications.
Level Indication

A suitable level sensor sends a switching signal to the PLC input.

Illustrative PLC cabinet and field sensor cable used in machine-status monitoring.
Machine Status

A compatible field device reports a machine condition to a control module.

An ordinary PLC input and process sensor are not automatically suitable for a personnel-protection safety function. Such functions require the appropriate safety-rated devices and system design.

Why Is the Input Not Switching?

If a PNP sensor appears to change state but the PLC does not, first compare the actual sensor output type and input-module wiring diagram. Then check the input-group common, supply reference, ON/OFF voltage thresholds, output current capacity and any input filter or software inversion. A controller indicator may not describe the electrical state at the terminal; the exact module manual controls the interpretation.

Frequently Asked Questions

What does “sinking input” mean in a PLC?

It means the DC input circuit provides a current path from its input terminal toward the supply return. A compatible field device supplies current into that input when ON.

Which sensor output works with a sinking input?

A PNP sourcing output is the conventional match. Confirm the actual input module's wiring diagram, common and electrical ratings before connecting a specific sensor.

Does a sinking input work with an NPN sensor?

Not in the conventional direct three-wire pairing: an NPN sensor sinks current and normally pairs with a sourcing PLC input. A configurable sink/source input module may support either arrangement when its common is wired as specified.

Is a sinking input active low?

Typically no. In the conventional PNP-to-sinking-input circuit, the ON sensor sources a positive signal into the input. Controller program logic or labels may invert the displayed state, so check the module's electrical specification and configuration.

How can I identify my module's input type?

Use the exact input module model and wiring diagram. Check which supply polarity connects to the group's common terminal and whether the module expects a sourcing PNP or sinking NPN field output.