One-way is not loop length
Measure the installed run once from panel to sensor. The basic calculation accounts for both +V and 0V conductors; doubling the entered length again would double-count the loop.
XSZ engineering tool
Estimate how much DC supply voltage is lost along a sensor cable, then compare the remaining voltage with the minimum required by your exact sensor model.
Calculate the supply path
Use the lowest supply voltage expected at the cable origin and the current and conductor resistance expected in operation. This is a low-voltage DC cable estimate, not a wiring approval.
A DC conductor has resistance. Current through the supply wire and return wire creates voltage drop in both, so the voltage across the sensor can be lower than the voltage at the panel.
Measure the installed run once from panel to sensor. The basic calculation accounts for both +V and 0V conductors; doubling the entered length again would double-count the loop.
Conductor diameter alone does not capture every cable construction or temperature. Use a manufacturer’s per-conductor resistance for the actual cable, ideally adjusted or measured for operating conditions.
Use the exact model’s minimum supply voltage—not a generic percentage rule. A calculated margin is only one part of a complete wiring and operating check.
A circuit that appears fine at a bench supply may reach a lower voltage at the remote sensor, especially when the source is at its low end or current rises during operation.
Measure or specify the minimum voltage available at the cable origin under realistic loading. A nominal “24 V” label may not describe the worst case.
In a simple two-conductor feed, outgoing and return currents match. With a three-wire NPN/PNP sensor or shared supply, trace which wire carries each current.
After installation, measure across the sensor’s +V and 0V terminals while the machine runs. Compare that reading with the model range and the calculation.
Illustrative cable-only case: a 50 m one-way run, 100 mA in both conductors, 58 Ω/km per conductor and 24 V at the cable origin.
Estimate loss from a distant control cabinet to a photoelectric sensor, then measure voltage at the sensor while the conveyor is operating.
Each cable segment carries the current of devices downstream from it. Model segments separately; a single sensor-current entry cannot represent the whole shared network.
Use the advanced inputs only after tracing +V and 0V currents. Check the separate NPN/PNP output-wire path and PLC input thresholds independently.
Enter the one-way panel-to-sensor length once. In basic mode, the formula includes both the outgoing +V wire and returning 0V wire.
No. It only compares this cable estimate with the specified minimum sensor supply. Confirm the exact model’s maximum voltage, current, output type, load, PLC input, transient conditions and measured voltage at the terminals.
The tool asks for resistance because cable construction and temperature matter. Find the maximum conductor resistance in the actual cable datasheet or use a suitable measured value; do not assume one resistance for every cable with the same nominal gauge.
No. It estimates the sensor supply between +V and 0V. The separate output lead, PLC input threshold, load wiring and any voltage drop along that signal path require their own circuit check.
They are excluded. Poor contacts, extra connectors and corrosion can add loss. Measure the installed circuit under load and investigate any difference from the cable-only estimate.
Not as an approval tool. The calculation is a steady-state DC conductor estimate. AC impedance, IO-Link communication behavior, safety requirements, transients and voltage ripple need the relevant system documentation and testing.
Share the sensor model, cable part number and length, supply range, current path, connector count and controller input. XSZ can review the full installation requirements.
Technical background: Fluke, voltage drop and Ohm’s law; Fluke, outgoing and return conductor losses; Phoenix Contact, example sensor-cable resistance. These sources explain the method and one example cable; they are not XSZ model specifications.